Johnson Controls P20DB-1C

Johnson Controls Penn P20 P20DB-1C Pressure Cut-out Limit Control

Brand: Johnson Controls

Item No: P20DB-1C

Sign In for Availability
loading

Description

The P20 series are field replacement high and low pressure controls for non-corrosive refrigerants. They include a dust-tight contact unit with quick connect connectors and a 36 in or 42 in capillary with 1/4 in sweat section. The setpoint is screwdriver adjustable.

Johnson Controls Penn Pressure Cut-out Limit Control, Series: P20, Switching Action: Open on Rise, 100 - 425 lb/sq-in, 400 lbf/sq-in Open, 450 lbf/sq-in Maximum Bellows Pressure, 16 A Full Load, 96 A Locked Rotor, 16 A Non-Inductive at 120 VAC, 9.2 A Full Load, 55.2 A Locked Rotor, 16 A Non-Inductive at 208 VAC, 8 A Full Load, 48 A Locked Rotor, 16 A Non-Inductive at 240 VAC, 7 A Full Load, 42 A Locked Rotor at 277 VAC, Pilot Duty - 125 V-A at 24 VAC, 720 V-A at 277 VAC Contact, 36 in Capillary Length, 1/4 in Sweat Tube Connection, NEMA 1 Enclosure, 140 deg F

Features

  • Accurate repeatability
  • Compact size
  • Trip-free manual reset

Specifications

Capillary Length

36 in

Connection Size

1/4 in Sweat Tube

Contact Rating

16 A Full Load, 96 A Locked Rotor, 16 A Non-Inductive at 120 VAC, 9.2 A Full Load, 55.2 A Locked Rotor, 16 A Non-Inductive at 208 VAC, 8 A Full Load, 48 A Locked Rotor, 16 A Non-Inductive at 240 VAC, 7 A Full Load, 42 A Locked Rotor at 277 VAC, Pilot Duty - 125 V-A at 24 VAC, 720 V-A at 277 VAC

Enclosure Type

NEMA 1

Pressure Rating

100 - 425 lb/sq-in, 400 lbf/sq-in Open, 450 lbf/sq-in Maximum Bellows

Series

P20

Switching Action

Open on Rise

Temperature Rating

140 deg F

Documentation

Catalog

https://assets.unilogcorp.com/267/ITEM/DOC/Johnson_Controls_P266BHA_100C_Catalog.pdf

Instruction/Installation Manual

https://assets.unilogcorp.com/267/ITEM/DOC/Johnson_Controls_P20DB_1C_Manual.pdf

Specification Sheet

https://assets.unilogcorp.com/267/ITEM/DOC/Johnson_Controls_P20EB_2C_Specification_Sheet.pdf